Sign In | Join Free | My bjjsgy.com |
|
Brand Name : ABB
Model Number : AI815
Place of Origin : India (IN)
MOQ : 1
Price : Negotiations
Delivery Time : 2-3 working days
Packaging Details : New original box
Signal Specification : 0..20 MA, 4..20 MA, 0..5 V, 1..5 V
Under/over Range : 0 / +15%
Input Filter (rise Time 0-90%) : 290 Ms
Power Dissipation : 3.5W
AI815 3BSE052604R1 I/O Modules - System 800xA hardware selector Digital I O Module
General info:
Type |
Analog Input |
Signal specification |
0..20 mA, 4..20 mA, 0..5 V, 1..5 V |
Article number |
3BSE052604R1 |
Number of channels |
8 |
Signal type |
Unipolar single ended |
HART |
Yes |
SOE |
No |
Redundancy |
No |
High integrity |
No |
Intrinsic safety |
No |
Mechanics |
S800 |
Detailed data
Resolution |
12 bit |
Input impedance |
10 MΩ (voltage input) |
Isolation |
Groupwise isolated from ground |
Under/over range |
0 / +15% |
Error |
Max. 0.1% |
Temperature drift |
Max. 50 ppm/°C |
Input filter (rise time 0-90%) |
290 ms |
Update cycle time |
10 ms |
Current limiting |
Built in current limited transmitter power |
Maximum field cable length |
600 meters (656 yards) |
NMRR, 50Hz, 60Hz |
> 40 dB |
Rated insulation voltage |
50 V |
Dielectric test voltage |
500 V a.c. |
Power dissipation |
3.5 W |
Current consumption +5 V Modulebus |
100 mA |
Current consumption +24 V Modulebus |
Max. 265 mA (22 mA + 1.32 * transmitter current) |
Current consumption +24 V external |
50 mA |
Diagnostics:
Front LED’s |
F(ault), R(un), W(arning) |
Supervision |
Module error, if: analog read back, reference voltage, internal power supply, checksum, watchdog and memory error |
Status indication of supervision |
Module Error, Module Warning, Channel error |
CE mark | Yes |
Electrical safety | IEC 61131-2, UL 508 |
Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
Marine certification | BV, DNV-GL, LR |
Protection rating | IP20 according to IEC60529 |
Corrosive atmosphere ISA-S71.04 | G3 |
Climatic operating conditions | 0 to +55 °C (Storage -40 to +70 °C), RH=5 to 95 % no condensation, IEC/EN 61131-2 |
Pollution degree | Degree 2, IEC 60664-1 |
Mechanical operating conditions | IEC/EN 61131-2 |
EMC | EN 61000-6-4, EN 61000-6-2 |
Overvoltage categories | IEC/EN60664-1, EN 50178 |
Equipment class | Class I according to IEC 61140; (earth protected) |
Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
RoHS compliance | EN 50581:2012 |
WEEE compliance | DIRECTIVE/2012/19/EU |
![]() |